Description
Features
NetShelter Aisle Containment Active Flow Controller APC
- Centralised controller for temperature and cooling in data centres
- The controller works by sensing pressure inside the aisle to adjust cooling unit fan speed. This prevents forced-mixing of hot and cold air.
- The Active Flow Controller is also useful in situations where a rack’s CFM/kW fluctuates throughout the day.
- Depth 10.7 cm
- Height 4.1 cm
- Weight 0.44 kg
- Width 17.3 cm
- The zero-point accuracy is +/-0.0004 inches WC. The accuracy over the entire span of the sensor is 3% of the measurement, or +/- 0.003 inches WC maximum at full scale.
- Data centre airflow controller for thermal containment applications
- Applications
Small to Large Data Centers
EcoAisle Thermal Containment
Rack Air Containment (RACS) - It is a ΔP (pressure) controller – an alternative to traditional data centre ΔT control. The device samples pressure inside and outside the thermal containment system and communicates with the cooling units to right-size airflow. The controller accomplishes this by adjusting the cooling units’ fan speed to ensure the desired volume of air reaches the IT equipment. It is compatible with EcoAisle Thermal Containment and Rack Air Containment (RACS); as well as firmware compatible with many of Schneider Electric cooling products.













Milex Bamboo Lid Glass Container Set 3 piece
Forbatt rechargeable gel battery 12V 18Ah
Huawei Band 11 smart watch
JA Solar 595W n-type Bifacial Double Glass high efficiency mono solar panel
Simply Bee Horse hoof balm 1kg
Solar MD 128kW HV Battery
NH Fuse-link 400A for Keto 3
Staycold HD1140 Double Hinged Door Upright Cooler
Okiyo Koruku Cork & Cotton Toiletry Bag
Soaring Free Organic Matcha Tea Powder 70g box of 6
Outdo motorcycle battery 12V 6.5Ah HCZ7S-BS
Axpert 5kW hybrid inverter Lynx 5000-48
Reviews
There are no reviews yet.